🏥🇺🇸WELL v2 Feature 74 · Global

Hospital Ward Acoustic Design in United StatesWELL v2 Feature 74 Requirements

Patient wards, recovery rooms, consultation rooms. Typical volume: 100-500 m³.

RT60 Target
≤ 0.6s
Background Noise
≤ 35 dBA
STI Requirement
≥ 0.60
Regulation
WELL v2 for Healthcare
RT60 (Reverberation Time)
The time, in seconds, for sound to decay by 60 dB after the source stops. WELL v2 Feature 74 requires ≤ 0.6s for hospital ward spaces in United States.
Reference: WELL v2 for Healthcare — FGI Guidelines

What WELL v2 Feature 74 Requires for a Hospital Ward in United States

Regulation: WELL v2 for Healthcare — FGI Guidelines

RT60 target: ≤ 0.6s

Background noise limit: ≤ 35 dBA

STI requirement: ≥ 0.60

Local note: FGI 2022 Guidelines require acoustic analysis for all US healthcare over 5,000 sq ft.

How to Calculate WELL v2 Feature 74 Compliance for a Hospital Ward in United States

  1. 1

    Identify the applicable United States standard and target

    Look up WELL v2 Feature 74 for hospital ward spaces in United States. The RT60 target is ≤ 0.6s. WELL v2 for Healthcare — FGI Guidelines.

  2. 2

    Measure or model the room geometry

    Record the length, width, and height of the room to calculate the volume. A typical hospital ward has a volume of 100-500 m³.

  3. 3

    List all surfaces and their absorption coefficients

    For each surface (floor, ceiling, walls, windows, doors), find the absorption coefficient at each octave band frequency (125 Hz to 4 kHz) from ISO 354 test data or a materials database.

  4. 4

    Calculate total absorption and apply the Sabine or Eyring equation

    Sum all surface absorption values: A = sum of (alpha x area). Then apply T60 = 0.161 x V / A (Sabine) or T60 = -0.161 x V / (S x ln(1 - alpha_avg)) (Eyring). Use Eyring when average alpha exceeds 0.20.

  5. 5

    Compare result against WELL v2 Feature 74 and specify treatment

    If the calculated RT60 exceeds the target of ≤ 0.6s, specify additional absorption. Typical treatment cost in United States is $28,000–$45,000 per 100m².

Cost of Compliance in United States

Treatment Cost Range

$28,000–$45,000 per 100m²

Currency: $

What Affects Cost

  • • Room volume and surface area
  • • Target standard strictness
  • • Existing acoustic conditions
  • • Finish and material quality

Frequently Asked Questions

What RT60 does WELL v2 Feature 74 require for a hospital ward in United States?

WELL v2 Feature 74 requires a reverberation time of ≤ 0.6s for hospital ward spaces in United States. WELL v2 for Healthcare — FGI Guidelines. Measurement should be performed per ISO 3382-2 methodology.

What is the background noise limit for a hospital ward in United States?

The background noise limit is ≤ 35 dBA under WELL v2 Feature 74. This typically refers to HVAC and building services noise measured with the room unoccupied.

How much does acoustic treatment cost for a hospital ward in United States?

Typical acoustic treatment for a hospital ward in United States costs $28,000–$45,000 per 100m². Costs vary based on finish quality, room size, and existing conditions.

Calculate WELL v2 Feature 74 Compliance for Your Hospital Ward in United States

Enter your room dimensions, select materials, and instantly verify compliance against WELL v2 Feature 74. Free, no signup required.

Open Free RT60 Calculator