Worked Example: Conference Facility — DIN 18041 Speech Clarity

HospitalityDIN-18041IntermediateMARGINAL

500 m³ conference room with Rockfon ceiling, carpet, and fabric panel walls

TL;DR

A 500 meeting room designed to DIN-18041 requires RT60 ≤ 0.7s. With Rockfon Sonar 25mm ceiling tile on the ceiling and Fabric-wrapped panel 50mm on walls, the calculated RT60 is 0.43s MARGINAL.

Room Setup

Length
25 m
Width
10 m
Height
2 m
Volume
500 m³

Total surface area: 633.0 m². Calculation method: Sabine equation (ISO 3382-2:2008 Annex A).

Surface Materials

SurfaceMaterialArea (m²)NRC
Ceiling — Rockfon SonarRockfon Sonar 25mm ceiling tile100.00.82
Ceiling — plasterPainted plaster150.00.04
FloorHeavy carpet250.00.29
Walls — plasterboardPlasterboard on studs80.00.07
Walls — fabric panelsFabric-wrapped panel 50mm12.00.78
Projection wallPainted plaster20.00.04
WindowsDouble glazing 6mm14.00.03
DoorsSolid timber door7.00.09

Absorption coefficients sourced from manufacturer datasheets and ISO 354 test reports. Browse the full acoustic materials database.

Step-by-Step Calculation

  1. 1

    Room Volume

    V = L × W × H = 25 × 10 × 2 = 500

  2. 2

    Total Surface Area

    Stotal = 100.0 + 150.0 + 250.0 + 80.0 + 12.0 + 20.0 + 14.0 + 7.0 = 633.0

  3. 3

    Absorption per Surface at 500 Hz

    Ceiling — Rockfon Sonar: 100.0 m² × 0.82 = 82.00 Sabins

    Ceiling — plaster: 150.0 m² × 0.04 = 6.00 Sabins

    Floor: 250.0 m² × 0.14 = 35.00 Sabins

    Walls — plasterboard: 80.0 m² × 0.05 = 4.00 Sabins

    Walls — fabric panels: 12.0 m² × 0.78 = 9.36 Sabins

    Projection wall: 20.0 m² × 0.04 = 0.80 Sabins

    Windows: 14.0 m² × 0.04 = 0.56 Sabins

    Doors: 7.0 m² × 0.08 = 0.56 Sabins

  4. 4

    Total Absorption at 500 Hz

    Atotal = 82.00 + 6.00 + 35.00 + 4.00 + 9.36 + 0.80 + 0.56 + 0.56 = 138.28 Sabins

  5. 5

    Sabine RT60 at 500 Hz

    RT60 = 0.161 × V / A = 0.161 × 500 / 138.28 = 0.58s

  6. 6

    Compare to Target

    Mid-frequency RT60 (avg of 500, 1k, 2k Hz) = 0.43s. Target: 0.5--0.7s per DIN-18041. Verdict: MARGINAL

Octave Band Results

Frequency125Hz250Hz500Hz1kHz2kHz4kHz
Total Absorption (Sabins)64.8100.0138.3207.4263.7274.2
RT60 (s)1.240.810.580.390.310.29
Target (s)0.700.700.70
VerdictPASSFAILFAIL

Compliance Verdict

MARGINAL

Reference:

Reproduce This Example

Open the AcousPlan calculator pre-loaded with the exact room dimensions (25m × 10m × 2m) and RT60 target (0.7s).

Open Calculator

Field Story

A purpose-built conference centre in Frankfurt hosts international trade events requiring simultaneous interpretation. DIN 18041:2016 classifies this as a Group A room (speech communication), demanding reverberation between 0.5 and 0.7 seconds for 500 m³. Rockfon Sonar ceiling covers 60% of the ceiling area with consistent broadband absorption, the remaining 40% left as painted plaster above service zones. Heavy carpet absorbs footfall noise from 200 delegates between breakout sessions. Fabric-wrapped panels on the rear wall prevent late reflections degrading intelligibility for delegates furthest from the podium. Plasterboard partition walls separating concurrent sessions provide both sound insulation and low-frequency panel absorption. The combination of ceiling tiles and carpet provides the bulk of the mid-frequency absorption required.

Frequently Asked Questions

What RT60 does a Conference Facility — DIN 18041 Speech Clarity achieve?

With the specified materials and dimensions (25m x 10m x 2m, volume 500m3), the calculated mid-frequency RT60 is 0.43s using the Sabine equation. The target under DIN-18041 is 0.5--0.7s. The result is a MARGINAL.

What materials are used in this hospitality acoustic example?

This example uses Rockfon Sonar 25mm ceiling tile on the Ceiling — Rockfon Sonar (NRC 0.82), Painted plaster on the Ceiling — plaster (NRC 0.04), Heavy carpet on the Floor (NRC 0.29), Plasterboard on studs on the Walls — plasterboard (NRC 0.07), Fabric-wrapped panel 50mm on the Walls — fabric panels (NRC 0.78), Painted plaster on the Projection wall (NRC 0.04), Double glazing 6mm on the Windows (NRC 0.03), Solid timber door on the Doors (NRC 0.09). The total absorption at 500 Hz is 138.3 Sabins.

How much does acoustic treatment cost for this room?

Cost data is not available for this example. Use the AcousPlan calculator to estimate treatment costs for your specific room configuration.

Related Examples

Explore More

All calculations are advisory and based on the Sabine equation (ISO 3382-2:2008 Annex A). Results require professional verification for compliance submissions. Absorption coefficients are sourced from manufacturer datasheets and ISO 354 test reports.