Skip to main content
🏥ASHRAE 189.1-2020 · United States

Hospital Ward Acoustic Design to ASHRAE 189.1-2020

Hospital wards must balance patient recovery needs with staff communication requirements. Excessive noise is linked to disrupted sleep, elevated stress hormones, and slower healing.

TL;DR

Under ASHRAE 189.1-2020, a hospital ward of 250-350 m³ (typical dimensions 15m × 8m × 2.7m) requires an RT60 of ≤ 0.8s at broadband. Background noise must not exceed 35 NC. ASHRAE Handbook Chapter 49 recommends NC 25-30 for hospital patient rooms, which is stricter than the 40 dBA general guidance.

RT60 Target
≤ 0.8s
Noise Limit
35 NC
STI Minimum
N/A
Frequency Range
broadband

Specific Requirements

ParameterTargetClause ReferenceNotes
Background Noise Limit≤ 35 NC§8.3.4HVAC + building services, unoccupied
Frequency RangebroadbandOctave bands for compliance assessment

Step-by-Step Compliance Calculation

  1. 1

    Set NC 25-30 target

    Patient rooms: NC 25-30 per ASHRAE Chapter 49. Operating theatres: NC 35-40.

  2. 2

    Balance with ASHRAE 170

    Design ductwork to deliver required air changes while maintaining noise below NC curve at patient bed positions.

  3. 3

    Specify low-noise equipment

    Select AHUs, terminal units, and diffusers with published sound power data suitable for NC 25-30 target.

  4. 4

    Verify and commission

    Measure octave-band noise at patient bed positions with HVAC at full design conditions.

Recommended Materials

SurfaceMaterial CategoryMin NRCCoverage %
CeilingHealthcare ceiling tile0.8080%
Duct attenuationHospital-grade silencer0.70100%

Browse the full acoustic materials database for absorption coefficients and product specifications.

Common Failure Modes

⚠️ASHRAE 170 air change conflict

High air change rates required for infection control (6-12 ACH) demand large airflow volumes that generate significant duct noise.

⚠️Terminal reheat coil noise

Hospital zone reheat coils generate turbulent noise at the valve, radiating through ductwork to patient rooms.

Frequently Asked Questions

What RT60 does ASHRAE 189.1-2020 require for a hospital ward?

ASHRAE 189.1-2020 requires a reverberation time of ≤0.8s at broadband for hospital ward spaces. ASHRAE Handbook Chapter 49 recommends NC 25-30 for hospital patient rooms, which is stricter than the 40 dBA general guidance. Hospital HVAC systems must be designed for very low noise output while maintaining the air changes required by ASHRAE 170 for infection control.

What is the maximum background noise level for a hospital ward under ASHRAE 189.1-2020?

ASHRAE 189.1-2020 sets a maximum background noise level of 35 NC for hospital ward spaces. This includes noise from HVAC systems, building services, and external intrusion, measured with the room unoccupied. Exceeding this limit degrades speech intelligibility and occupant comfort.

How much acoustic treatment does a hospital ward need to comply with ASHRAE 189.1-2020?

A typical hospital ward (250-350 m³) requires Healthcare ceiling tile (NRC ≥0.8) covering 80% of the ceiling as the primary treatment. Additional wall absorption on 1 surface(s) is typically needed. Use the AcousPlan calculator with the pre-loaded dimensions (12m × 8m × 3m) to calculate the exact absorption deficit for your room.

Calculate ASHRAE 189.1-2020 Compliance for Your Hospital Ward

Pre-loaded with typical hospital ward dimensions (12m × 8m × 3m) and an RT60 target of 0.8s per ASHRAE 189.1-2020. Enter your actual dimensions, select materials, and verify compliance instantly.

Open Calculator with Preset

Related Guides

Further Reading